Note:
When BFMM1E intelligent molded case circuit breaker is used for networking communication, it can be directly connected to the corresponding fieldbus; For Fieldbus with different protocols, cm-dp protocol conversion module can be selected to convert Modbus protocol and connect it to corresponding fieldbus.
When the BFMM1E-type communication intelligent plastic shellcircuit brelaker sets the protection parameters of the circuit breaker alone, the professionals should connect with the Fl handheld programmer according to the figure below, and then follow the operation instructions of the handheld programmer
BFMM1E communication intelligent molded case circuit breaker is used together with LCD module. During normal operation, the display module can monitor the operating current and fault information of the circuit breaker. When seting the protection parameters of circuit breaker, professionals need to use LK handheld programmer to connect, and then operate according to the operation instructions of handheld programmer.
The communication network of BFMM1E communication intelligent molded case circuit breaker can be connected by referring to the scheme in the figure below. Different protocol modules can be selected for different protocols to convert MODBUS into PROFIBUS-DP and other protocols.
| Long delay fault | Short delay fault | Ground fault |
| Leakage fault | Transient fault | Overvoltage fault |
| Temperature overtemperature fault |
Fault trip | Undervoltage fault |
| Long delay fault alarm | Short delay fault alarm | Earth fault alarm |
| Long delay fault | Short delay fault | Ground fault |
| Leakage fault alarm | Instantaneous fault alarm |
Overvoltage fault alarm |
| Temperature over temperature fault alarm |
Fault trip alarm | Undervoltage fault alarm |
Opening and closing state detection function of circuit breaker (optional function); The controller can detect the current opening and closing state of the circuit breaker and upload it to the host computer to the computer network in real time.
Front indication of circuit breaker






Note:
1 – overload long delay action current LR1 adjustment, which can be adjusted from gear 4 to gear 10 according to different rated currents of the circuit breaker:
2- long delay action time T1 adjustment, 4-gear adjustment can be carried out:
3- short circuit short delay action cuent LR 2 adjustment, 10 gear adjustment can be carried out;
4- short delay action time T2 adjustment, 4-gear adjustment can be carried out;
5- short circuit instantaneous action current LR3 adjustment, which can be adjusted in gear 8, 9 or 10; The alarm current can be adjusted in r7-gear and l6-gear.
7 – test end, used for sub release test (test).
| Model | BFMM1E-125 | BFMM1E-250 | |||||
| Frame level current Inm (A) | 125 | 250 | |||||
| Rated current (adjustable) In (A) | 16,20,25,32 | 32,36,40,45 50,55,60,63 |
63,65,70,75,80, 85,90,95,100,125 |
100,125,140,160, 180,200,225,250 |
|||
| Rated working voltage Ue (V) | AC 400V | ||||||
| Rated insulation voltage UI (V) | AC 800V | ||||||
| Rated impulse withstand voltage Uimp | AC 400V | AC 800V | |||||
| Number of poles (P) | 3 | 4 | 3 | 4 | |||
| Rated limit short circuit breaking capacity level |
S | H | H | S | H | H | |
| Rated limit short circuit breaking capacity LCU (kA) |
35 | 70 | 70 | 35 | 70 | 70 | |
| Rated operating short-circuit breaking capacity LCS (kA) |
25 | 50 | 50 | 25 | 50 | 50 | |
| Use category | A | AC 800V | |||||
| Operating performance (Times) |
Electrify | 3000 | 3000 | ||||
| No electricity | 7000 | 7000 | |||||
| Overall dimension (mm) ![]() |
L | 150 | 165 | ||||
| M | 92 | 122 | 107 | 142 | |||
| H | 92 | 90 | |||||
| Flying fox distance | ≤50 | ≤50 | |||||
| Model | BFMM1E-400 | BFMM1E-630 | BFMM1E-800 | |||||
| Frame level current Inm (A) | 400 | 630 | 800 | |||||
| Rated current (adjustable) In (A) | 200,225,250,280, 315,350,400 |
400,420,440,460,480, 500,530,560,600,630 |
630,640,660,680,700, 720,740,760,780,800 |
|||||
| Rated working voltage Ue (V) | AC 400V | |||||||
| Rated insulation voltage UI (V) | AC 800V | |||||||
| Rated impulse withstand voltage Uimp | AC 8000V | |||||||
| Number of poles (P) | 3 | 4 | 3 | 4 | 3 | 4 | ||
| Rated limit short circuit breaking capacity level |
S | H | H | S | H | M | H | |
| Rated limit short circuit breaking capacity LCU (kA) |
50 | 70 | 70 | 70 | 70 | 70 | 70 | |
| Rated operating short-circuit breaking capacity LCS (kA) |
35 | 50 | 50 | 50 | 50 | 50 | 50 | |
| Use category | B | B | B | |||||
| Operating performance (Times) |
Electrify | 2000 | 1500 | 1500 | ||||
| No electricity | 4000 | 3000 | 3000 | |||||
| Overall dimension (mm) ![]() |
L | 257 | 257 | 257 | ||||
| M | 150 | 198 | 150 | 198 | 210 | 280 | ||
| H | 106.5 | 115.5 | 115.5 | |||||
| Flying fox distance | ≤106.5 | ≤100 | ≤100 | |||||
| Controller type | Basic type | Intelligent communication type, programming communication type, LCD type | |
| 2Ir1 | Inm=125A、250A Setting time t1(s) | <1h action t1=(12,60,80,100)s t1=(12,60,100,150)s |
12s-100s(Maximum step1s) 12s-150s(Maximum step1s) |
| Inm=400A、630A、800A Setting time t1(s) | |||
| Thermal memory | After 30 min,it can be cleared after power failure (this function is optional for intelligent communication type and programmed communication type) |
||
| 1.The action time complies with 12t1 = (2Ir1) 2t1(1.2Ir1 <I<LR1;2.The allowable difference of action time is ± 20%; 3.The returnable time is not less than 70% of the action time. |
|||
| Current(A) | Action time | |||||
| Lr2<l<1.51r2 | Inverse time limit | |||||
| 1.51r2<l<Ir3 | Time limit | Setting time T2 (s) | 0.06 | 0.1 | 0.2 | 0.3 |
| Tolerance (s) | ±0.02 | ±0.03 | ±0.04 | ±0.06 | ||
| Returnable time (s) | 0.14 | 0.21 | ||||
| Note: the allowable deviation of inverse time action time is ± 20% a | ||||||
| Rated current(A) | Rated current(A) | Action characteristics |
| 100、225 | Ir3=4、6、7、10、11、12、13、14、16 | |
| 400、635 | Ir3=4、6、7、10、11、12、13、14 | I<0.85Ir No action I>1.15lr3 action |
| 800 | Ir3=4、6、7、8、9、10、11、12 |
Front wiring of BFMM1E-125H board (two pole, three pole and four pole)(x-x and Y-Y are the center of three pole circuit breaker)

| Model | H | H1 |
| BFMM1E-125H | 86 | 104 |
| BFMM1E-125H Level 4 |
Front wiring of BFMM1E-250H board (three pole and four pole) (x-x and Y-Y are the center of three pole circuit breaker)

| Model | H | H1 |
| BFMM1E-125H | 105 | 127 |
Front wiring of BFMM1E-400H board (three pole and four pole) (x-x and Y-Y are the center of three pole circuit breaker)

Front wiring of BFMM1E-630H board (three pole and four pole) (x-x and Y-Y are the center of three pole circuit breaker)

Front wiring of BFMM1E-8ooH board (three pole and four pole) (x-x and Y-Y are the center of three pole circuit breaker)