BFMM8-PV Photovoltaic DC Circuit Breakers

BEMM8-PV series photovoltaic DC circuit breakers are applicable to DC power grid circuits with rated voltage up to DC1oooV and rated current up to 1250A.DC circuit breaker has the functions of overload long-time delay protection and short- circuit instantaneous protection. which is used to distribute electric energy and protect lines and power supply equipment from overload and shot circuit and other faults. The operating mechanism of DC circuit breaker has the functions of fast closing and fast breaking, with compact structure,small volume and convenient use.

Model And Meaning

BFMM PV Photovoltaic DC Circuit Breakers Model And Meaning ①Note: operating voltage of electric operating mechanism:AC110V、AC220v、DC24V、DC110V、DC220V。 ② Note: the shell frame grade of Y2 and Y2B > 40oA is not applicable to internal links.

Normal Operating Conditions

  • if the altitude is 2ooom or below, it needs to be reduced for use if it is higher than 2ooom. Please contact the manufacturer for other special requirements;
  • be able to withstand the influence of humid air (three prevention type) ①;
  • be able to withstand the influence of salt mist and oil mist (three prevention type);
  • be able to withstand the influence of mold (three prevention type);
  • in the medium without explosion hazard, and the medium is not enough to corrode metal and damage insulation
  • where gas and conductive dust are.
  • Note: ① for three prevention products, please indicate th.

Use And Maintenance

Various characteristics and accessories of the circuit breaker are set by the manufacturer and cannot be adjusted at will in use. Under the condition that the user abides by the storage and use conditions, no more than 18 months from the date of delivery by the manufacturer The seal of the road device is intact. If the product is damaged or cannot be used normally due to manufacturing quality problems, the manufacturer is responsible for replacing and repairing it free of charge.  

Accessories Code

Attachment name No enclosure call the
policecontact
Shunt de excitation
Buckle
auxiliary contact Undervoltage
release
Auxiliary contact of shunt release Undervoltage release shunt release Two sets of
auxiliary contacts
代号 00 08 10 20 30 40 50 60
Attachment name Auxiliary contact of
undervoltage release
Alarm contact
of shunt release
Auxiliary contact alarm contact Alarm contact of undervoltage release Auxiliary contact alarm
contact of shunt release
Two sets of auxiliary contacts and
alarm contacts
Auxiliary contact
undervoltage
release alarm
contact
代号 70 18 28 38 48 68 78

Electrical Technical Parameters

Model BFMM8-125PV BFMM8-250PV BFMM8-400PV BFMM8-630PV BFMM8-800PV BFMM8-1250PV
Rated continuous current Tnm 125 250 400 630 800 1250
Rated currentIn(A) 20,25,32,40,
50,63,80,100,125
125,140,160,180,
200,225,250
250,315,350,400 400,500,630 630,700,800 800,1000,
1250
Rated working voltage
Ue(V)DC
250V,500V,
750V,1000V
500V,
750V,1000V
500V,780V,1000V 500V,750V,
1000V
500V,750V,
1000V
500V,750V,
1000V
Rated insulation voltage
Ui (V)
1000V 1000V 1500V 1500V 1500V 1500V
Rated impulse withstand
voltage Uimp(kV)
8KV 8KV 8KV 8KV 8KV 8KV
Test pressure for one
minute(V)
3550 3550 3550 3550 3550 3550
Ultimate short
circuit breaking
capacity(kA)Icu
(Ics=75%lcu)
250V 20 20 35 35 50 50
500V 20 20 35 35 50 50
750V 20 20 35 35 50 50
100OV 20 20 35 35 50 50
Mechanical life Total
times
7000 7000 4000 4000 2500 2000
Electrical life Total
times
2000 2000 1000 1000 800 600
Total breaking time (MS) 20 20 20 20 20 20
Installation position Anywhere
Whether it has isolation
characteristics
Yes
standard IEC60947-2、IEC60947-1、GB14048.1、GB14048.2
Allowable ambient
temperature (C)
-25℃~+50℃
Degree of protection IP20
With accessories Auxiliary, alarm, shunt, manual operation, electric operation, machine interlocking
Arcing distance (mm) ≥50
Instantaneous action value 12In
Installation mode Fixed, plug-in

Classification

According to the operation mode: according to the form of protection: According to the wiring form:
Body direct operation: Line protection; Front panel wiring:
Operation of electric operating mechanism: Line isolation Wiring behind the board:
Rotate the handle for operation. Plug in wiring;
Draw out wiring (shell rack level current > 400A).

Wiring Method

Grounding type Single pole grounding system Ungrounded system
Circuit diagram BFMM PV Photovoltaic DC Circuit Breakers Wiring Method BFMM PV Photovoltaic DC Circuit Breakers Wiring Method
Fault effect Fault A Maximum short circuit currentlsc Fault A No effect
Fault B Maximum short circuit currentlsc Fault B Maximum short circuit currentlsc
Fault C No effect Fault C No effect
≤ DC500V BFMM PV Photovoltaic DC Circuit Breakers Wiring Method

Note: 1. Both upper and lower incoming
lines can be used. Here, the following incoming
lines are taken as an example

BFMM PV Photovoltaic DC Circuit Breakers Wiring Method

Note: 1. Both upper and lower incoming lines can be used.
Here, the following incoming lines are taken as an example to
ensure that there will be no secondary grounding fault in the
installation mode

DC500~750V BFMM PV Photovoltaic DC Circuit Breakers Wiring Method

Note: 1.Both upper and lower incoming
lines can be used. Here, the following incoming
lines are taken as an example

BFMM PV Photovoltaic DC Circuit Breakers Wiring Method

Note: 1. Both upper and lower incoming lines can be used.
Here, the following incoming lines are taken as an example to
ensure that there will be no secondary grounding fault in the
installation mode

DC750-1000V-1200V BFMM PV Photovoltaic DC Circuit Breakers Wiring Method

Note: 1. Both upper and lower incoming
lines can be used. Here, the following incoming
lines are taken as an example

BFMM PV Photovoltaic DC Circuit Breakers Wiring Method

Note: 1. Both upper and lower incoming lines can be used.
Here, the following incoming lines are taken as an example to
ensure that there will be no secondary grounding fault in the
installation mode

  • Inter pole series technology: it can bear higher voltage, and series accessories can reduce the temperature rise caused by inter pole series.
  • Inter pole parallel technology: balance the current flowing through each pole and can bear 2, 3 and 4 times the rated current.

Action Characteristic Curve

BFMM PV Photovoltaic DC Circuit Breakers Action Characteristic Curve

Outline And Installation Dimension Drawing

 

BFMM PV Photovoltaic DC Circuit Breakers Outline And Installation Dimension Drawing

 

Model A B ΦC L W C D G I W1 E F ФD H H1 H2 H3 H4
BFMM8-125PV 30 129 4.5 150 122 91 64 18 131 30 57 24 8 97 107 28 89.5 83
BFMM8-250PV 35 127 4.5 166 142 95 96 23 146 35 57 24 8 97 107 28 89.5 83
BFMM8-400PV 44 195 7 259 199 173 128 30 228 44 89 65 10 108 153 36 103 99
BFMM8-630PV 58 236 7 270 243 184 134 43 235 58 89 65 12 112 158 40 109 104
BFMM8-800PV 70 243 7 280 272 205 155 46 243 70 105 66 12 108 158 32 103 99
Welcome to our website. If you have any requests or suggestions,please feel free to email us at  [email protected] or use the following enquiry form. Please allow us to provide you with the best service.

Other Related Products

A
Welcome to our website. If you have any requests or suggestions,please feel free to email us at  [email protected]  or use the following enquiry form. Please allow us to provide you with the best service.
Get A Quote
Welcome to our website. If you have any requests or suggestions,please feel free to email us at  [email protected]  or use the following enquiry form. Please allow us to provide you with the best service.
Select Language:
Welcome to our website. If you have any requests or suggestions,please feel free to email us at  [email protected]  or use the following enquiry form. Please allow us to provide you with the best service.